- Description: Power Supply | SLC 500
- Line Voltage: 85-132/170-265V ac 47-63 Hz
- Typical Line Power Requirement: 240 VA
- Maximum Inrush Current: 45A
- Internal Current Capacity: 10.0A at 5V dc 2.88A at 24V dc
- Fuse Protection: Fuse is soldered in place.
- 24V dc User Power Current Capacity: 1A
- 24V dc User Power Volt. Range: 20.4-27.6V dc
- Max. User-supplied overcurrent protection: 15A
- Ambient Operating Temperature: 0C to +60C (+32F to +140F) no derating
- Isolation: 2600V dc for 1 s
- CPU Hold-up Time: 20 ms (full load) 3000 ms (no load)