- Description: TeSys F contactor - 3P(3 NO) - AC-3 - <= 440 V 330 A - without coil
- Product weight: 20.94 lb(US) (9.5 kg)
- IP degree of protection: IP20 front face with shrouds (ordered separately) conforming to IEC 60529, IP20 front face with shrouds (ordered separately) conforming to VDE 0106
- Standards: IEC 60947-4-1, EN 60947-1, EN 60947-4-1, JIS C8201-4-1, IEC 60947-1
- Device short name: LC1F
- Width: 8.39 in (213 mm)
- Height: 8.11 in (206 mm)
- Depth: 8.62 in (219 mm)
- Protective treatment: TH
- [Ui] rated insulation voltage: 1000 V conforming to IEC 60947-4-1, 1500 V conforming to VDE 0110 group C
- [Uimp] rated impulse withstand voltage: 8 kV
- Operating altitude: 9842.52 ft. (3000 m) without derating in temperature
- Tightening torque: Power circuit: 309.73 lbf.in (35 N.m)
- Connections - terminals: Power circuit: lugs-ring terminals 1 cable(s) 0.37 in (240 mm), Power circuit : bar 2 x (30 x 5 mm)
- Range: TeSys
- Mounting support: Plate
- [Ith] conventional free air thermal current: 400 A at <= 104 F (40 C)
- System Voltage: <= 1000 V AC 50/60 Hz, <= 460 V DC
- Product name: TeSys F
- motor power kW: 160 kW at 380...400 V AC 50/60 Hz AC-3, 200 kW at 500 V AC 50/60 Hz AC-3, 180 kW at 415 V AC 50/60 Hz AC-3, 200 kW at 440 V AC 50/60 Hz AC-3, 160 kW at 1000 V AC 50/60 Hz AC-3, 59 kW at 400 V AC 50/60 Hz AC-4, 100 kW at 220...240 V AC 50/60 Hz AC-3, 220 kW at 660...690 V AC 50/60 Hz AC-3
- [Ie] rated operational current: 400 A (<= 104 F (40 C)) at <= 440 V AC AC-1, 330 A (<= 131 F (55 C)) at <= 440 V AC AC-3
- Utilization category: AC-1, AC-4, AC-3
- Poles description: 3P
- Overvoltage category: III
- Associated fuse rating: 400 A aM at <= 440 V, 500 A gG at <= 440 V
- Product or component type: Contactor
- Ambient air temperature for operation: 23...131 F (-5...55 C)
- Irms rated making capacity: 3300 A AC conforming to IEC 60947-4-1
- Ambient air temperature for storage: -76...176 F (-60...80 C)
- Contactor application: Motor control, Resistive load
- Rated breaking capacity: 2640 A conforming to IEC 60947-4-1
- Permissible ambient air temperature around the device: -40...158 F (-40...70 C)
- [Icw] rated short-time withstand current: 2650 A <= 104 F (40 C) 10 s, 1800 A <= 104 F (40 C) 30 s, 1300 A <= 104 F (40 C) 1 min, 900 A <= 104 F (40 C) 3 min, 750 A <= 104 F (40 C) 10 min
- Mechanical robustness: Vibrations contactor closed 5 Gn, 5...300 Hz, Vibrations contactor open 2 Gn, 5...300 Hz, Shocks contactor closed 15 Gn for 11 ms, Shocks contactor open 6 Gn for 11 ms
- Pole contact composition: 3 NO
- Average impedance: 0.28 mOhm at 50 Hz - Ith 400 A
- Power dissipation per pole: 31 W AC-3, 44 W AC-1
- Product certifications: UL, ABS, LROS (Lloyds register of shipping), RINA, CSA, RMRoS, BV, CB, DNV
Santa Clara Systems specializes in hard-to-find parts. Choose from our overstock inventory and save on LC1F330 . Santa Clara Systems carries 10,326 items from Telemecanique.
- Tesys F Contactor - 3p(3 No) - Ac-3 - <= 440 V 330 A - Without Coil
Alternates
Common Typos
- 1C1F330
- 1C1F33O
- 1CIF330
- 1CIF33O
- 1CLF330
- 1CLF33O
- IC1F330
- IC1F33O
- ICIF330
- ICIF33O
- ICLF330
- ICLF33O
- LC1F33O
- LCIF330
- LCIF33O
- LCLF330
- LCLF33O
Appended Numbers
- LC1F330-A
- LC1F330-B
- LC1F330-C
- LC1F330-D
- LC1F330-E
- LC1F330-F
- LC1F330-G
- LC1F330-H
- LC1F330-I
- LC1F330-J
- LC1F330-K
- LC1F330-L
- LC1F330-M
- LC1F330-N
- LC1F330-O
- LC1F330-P
- LC1F330-Q
- LC1F330-R
- LC1F330-S
- LC1F330-T
- LC1F330-U
- LC1F330-V
- LC1F330-W
- LC1F330-X
- LC1F330-Y
- LC1F330-Z
We Deliver!
- ✓ Late West Coast Shipping (5PM PST)
- ✓ Drop-Ship and Blind-Ship Specialists
- ✓ Expertly Packed Static-Limited
- ✓ Same-Day Service
- ✓ In-House Courier